Cable Description
- Cable Size: 95 mm²
- Standard Specification Applied To Cable: IEC 60502 - IEC 60228
- Rated Voltage: 600 / 1000 Volt
- Cable Description: Flexible Copper Conductor Insulated With Polyvinyl Chloride And Sheathed With Polyvinyl Chloride (CU / PVC / PVC)
Conductor
- Standard Specification Applied To Conductor: IEC 60228
- No. Of Cores Per Cable: 1
- Nominal Cross-Sectional Area Per Core: 95 mm²
- Nominal Number Of Strands Per Core: 1330
- Diameter Of Each Strand: 0.30 mm
- Cross-Sectional Area Of Each Strand: 0.07065 mm²
- Material Of Core: Copper
- Type: Class-5
- Overall Diameter Of Conductor: 14.70 mm
- D.C. Resistance Of Conductor At 20°C Per Km (Max.): 0.206 Ω/km
Insulation
- Material Of Insulation: Polyvinyl Chloride (PVC)
- Colour Per Core: ………
- Nominal Thickness Of Insulation Per Core: 1.60 mm
- Min. Insulation Resistance Per Core Per Km Length Of Cable At 70°C: 0.0032 MΩ.Km
- Test Voltage Between Cores And Earth: 3000V for 5 min
- Heat Resistance Test: 150°C for 1 hour
Over Sheath
- Material Of Outer Jacket: Polyvinyl Chloride (PVC)
- Thickness Of Outer Jacket: 1.60 mm
- Colour Of Outer Jacket: ………
Cable Dimension (Nominal)
- Approx. External Cable Diameter: 21.10 mm