Cable Description
- Cable Size: 25 mm²
- Standard Specification Applied To Cable: IEC 60502 - IEC 60228
- Rated Voltage: 600 / 1000 Volt
- Cable Description: Stranded Copper Conductor Insulated With Polyvinyl Chloride And Sheathed With Polyvinyl Chloride (CU / PVC / PVC)
Conductor
- Standard Specification Applied To Conductor: IEC 60228
- No. Of Cores per Cable: 1
- Nominal Cross-Sectional Area Per Core: 25 mm²
- Nominal Number Of Strands Per Core: 19
- Diameter Of Each Strand: 1.30 mm
- Material Of Core: Copper
- Type: Class-2
- Overall Diameter Of Conductor: 6.50 mm
- D.C. Resistance At 20°C: 0.727 Ω/km
Insulation
- Material Of Insulation: Polyvinyl Chloride (PVC)
- Colour Per Core: ………
- Nominal Thickness: 1.20 mm
- Insulation Resistance: 0.0050 MΩ.Km at 70°C
- Test Voltage: 3000V for 5 min
- Heat Resistance Test: 150°C for 1 hour
Over Sheath
- Material: Polyvinyl Chloride
- Thickness: 1.40 mm
- Colour: ………
Cable Dimension (Nominal)
- External Diameter: 11.70 mm

Arabic