Cable Description
- Cable Size: 300 mm²
- Standard Specification Applied To Cable: IEC 60502 - IEC 60228
- Rated Voltage: 600 / 1000 Volt
- Cable Description: Stranded Copper Conductor Insulated With Polyvinyl Chloride And Sheathed With Polyvinyl Chloride (CU / PVC / PVC)
Conductor
- Standard Specification Applied To Conductor: IEC 60228
- No. Of Cores Per Cable: 1
- Nominal Cross-Sectional Area Per Core: 300 mm²
- Nominal Number Of Strands Per Core: 61
- Diameter Of Each Strand: 2.50 mm
- Cross-Sectional Area Of Each Strand: 4.906 mm²
- Material Of Core: Copper
- Type: Class-2
- Overall Diameter Of Conductor: 22.50 mm
- D.C. Resistance Of Conductor At 20°C Per Km (Max.): 0.0601 Ω/km
Insulation
- Material Of Insulation: Polyvinyl Chloride (PVC)
- Colour Per Core: ………
- Nominal Thickness Of Insulation Per Core: 2.40 mm
- Min. Insulation Resistance Per Core Per Km Length Of Cable At 70°C: 0.0030 MΩ·km
- Test Voltage Between Cores And Earth: 3000 V for 5 min
- Heat Resistance Test: 150°C for 1 hour
Outer Sheath
- Material Of Outer Jacket: Polyvinyl Chloride (PVC)
- Thickness Of Outer Jacket: 2.00 mm
- Colour Of Outer Jacket: ………
Cable Dimension (Nominal)
- Approx. External Cable Diameter: 31.30 mm